EasyPact EZC MCCB
Molded-case circuit breakers from 15 to 400 A, featuring fixed settings.
EasyPact EZC MCCB
Molded-case circuit breakers from 15 to 400 A, featuring fixed settings.
| รายการ (Spec) | ค่า (Value) |
| Range of product | EasyPact |
| Product or component type | Circuit breaker |
| Device short name | Easypact EZC250H |
| Circuit breaker name | Easypact EZC250H |
| Device application | Distribution |
| Poles description | 2P |
| Protected poles description | 2t |
| Network type | AC |
| DC | |
| Network frequency | 50/60 Hz |
| [In] rated current | 100,125,150,160,175,200,225,250 A at 40 °C |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 |
| 250 V DC conforming to IEC 60947-2 | |
| Breaking capacity code | H |
| Breaking capacity | 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
| 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 | |
| 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 | |
| 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 36 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 85 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 85 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 | |
| [Ics] rated service breaking capacity | 5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
| 15 kA at 125 V DC conforming to IEC 60947-2 | |
| 15 kA at 250 V DC conforming to IEC 60947-2 | |
| 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 100,125,150,160,175,200,225,250 A at 50 °C |
| Protection type | Overload protection |
| Short-circuit protection | |
| Pollution degree | 3 conforming to IEC 60664-1 |
| 3 conforming to IEC 947- | |
| Standards | GB/T 14048.2 |
| EN/IEC 60947-1 | |
| EN/IEC 60947-2 | |
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -35…85 °C |