QOvs Pro RCBO Miniature Circuit Breaker 1-Pole type, engineered for earth leakage and electric shock protection.

QOvs Pro RCBO Miniature Circuit Breaker

The QOvs Pro 1-Pole RCBO is engineered to meet international safety standards, complying with IEC 61009 and the Thai Industrial Standard TIS 909-2548. This device provides essential protection against earth leakage, electric shocks, overloads, and short circuits.

With rated breaking capacities of 6 kA and 10 kA, these units operate at 240/415 VAC and are designed for seamless installation in both consumer units and load centers, ensuring comprehensive electrical safety for residential and commercial applications.

QOvs Pro RCBO Miniature Circuit Breaker

The QOvs Pro 1-Pole RCBO is engineered to meet international safety standards, complying with IEC 61009 and the Thai Industrial Standard TIS 909-2548. This device provides essential protection against earth leakage, electric shocks, overloads, and short circuits.

With rated breaking capacities of 6 kA and 10 kA, these units operate at 240/415 VAC and are designed for seamless installation in both consumer units and load centers, ensuring comprehensive electrical safety for residential and commercial applications.

รายการ (Spec) ค่า (Value)
Circuit breaker application Distribution
Range Square D
Product name QOvs RCBO
Product or component type Residual current breaker with overcurrent protection (RCBO)
Poles description 1P + Ns
Earthing system TN
Curve code C
Earth-leakage sensitivity 10 mA
Breaking capacity 6000 A Icn at 230/240 V AC 50/60 Hz
Number of protected poles 1
Device location in system Outgoer
Network frequency 50/60 Hz
Network type AC
Trip unit technology Thermal-magnetic
[Ue] rated operational voltage 230/240 V AC 50/60 Hz
Residual current tripping technology Voltage dependent functional earth
Earth-leakage protection time delay Instantaneous
Earth-leakage protection class Type AC
[Icw] rated short-time withstand current Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity 6000 A at 230/240 V AC 50/60 Hz
Electrical insulation class Class II
Limitation class 3
[Ui] rated insulation voltage 400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 4 kV
Suitability for isolation Yes
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Plug-on
Mounting support Socket
Ambient air temperature for operation -15…60 °C
Ambient air temperature for storage -40…85 °C

ดาวน์โหลดคู่มือการใช้งาน

Model PDF Link
RCBO 10mA 1P 6kA  20A Click Here!
RCBO 10mA 1P 6kA  25A Click Here!
RCBO 10mA 1P 6kA  50A Click Here!
RCBO 30mA 1P 6kA  16A Click Here!
RCBO 30mA 1P 6kA  20A Click Here!
RCBO 30mA 1P 6kA  25A Click Here!
RCBO 30mA 1P 6kA  32A Click Here!
RCBO 30mA 1P 6kA  40A Click Here!
RCBO 30mA 1P 10kA  10A Click Here!
RCBO 30mA 1P 10kA  16A Click Here!
RCBO 30mA 1P 10kA  20A Click Here!
RCBO 30mA 1P 10kA  25A Click Here!
RCBO 30mA 1P 10kA  32A Click Here!