| รายการ (Spec) |
ค่า (Value) |
| Range of product |
EasyPact |
| Product or component type |
Circuit breaker |
| Device short name |
Easypact EZC100H |
| Circuit breaker name |
Easypact EZC100H |
| Device application |
Distribution |
| Poles description |
1P |
| Protected poles description |
1t |
| Network type |
DC |
| AC |
| Network frequency |
50/60 Hz |
| [In] rated current |
15,20,25,30,40,50,60 A at 40 °C |
| [Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage |
125 V DC conforming to IEC 60947-2 |
| 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code |
H |
| Breaking capacity |
10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 |
| 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 |
| 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 |
| 5 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 |
| 50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity |
5 kA at 125 V DC conforming to IEC 60947-2 |
| 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 |
| 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 |
| 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Suitability for isolation |
Yes conforming to IEC 60947-2 |
| Utilisation category |
Category A |
| Trip unit name |
TM-D |
| Trip unit technology |
Thermal-magnetic |
| Trip unit rating |
15,20,25,30,40,50,60 A at 50 °C |
| Protection type |
Short-circuit protection |
| Overload protection |
| Pollution degree |
3 conforming to IEC 60664-1 |
| 3 conforming to IEC 947-1 |
| Standards |
EN/IEC 60947-2 |
| GB/T 14048.2 |
| JIS C8201-2-2 |
| EN/IEC 60947-1 |
| IP degree of protection |
IP20 conforming to IEC 60529 |
| IK degree of protection |
IK07 conforming to IEC 62262 |
| Ambient air temperature for operation |
-25…70 °C |
| Ambient air temperature for storage |
-35…85 °C |
|
|
| Range |
Square D |
| Product name |
Square D Qovs |
| Device application |
Protection |
| Product or component type |
Miniature circuit-breaker |
| Poles description |
1P |
| Network type |
AC |
| Trip unit technology |
Thermal-magnetic |
| Standards |
IEC 60998-1 |
| Network frequency |
50/60 Hz |
| [Ics] rated service breaking capacity |
6000 A 100 % x Icn conforming to IEC 60998-1 |
| [Ui] rated insulation voltage |
500 V |
| [Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60998-1 |
| Contact position indicator |
Yes |
| Control type |
Toggle |
| Local signalling |
ON/OFF indication |
| Fault trip |
| Mounting mode |
Plug-on |
| Mounting support |
Socket |
| IP degree of protection |
IP20 conforming to IEC 60529 |
| IP40 (modular enclosure conforming to IEC 60529 |
| Pollution degree |
3 |
| Overvoltage category |
IV |
| Tropicalisation |
2 |
| Relative humidity |
95 % at 55 °C |
| Ambient air temperature for operation |
-5…60 °C |
| Ambient air temperature for storage |
-40…85 °C |